VT8600 Series BACnet
®
Integration Manual
22
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: (514 ) 321-4150
028-0437-00 www.viconics.com | sales@viconics.com March 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VT8600U5X00B INTEGRATION –
GRAPHICAL USER INTERFACE OBJECTS
Objects typically used in a GUI:
• RoomTemperature(AV100)
• OccupiedandUnoccupiedHeatSetpoints
(AV39 and AV43)
• OccupiedandUnoccupiedCoolSetpoints
(AV40 and AV44)
• OutdoorTemperature(AV101)
• SupplyTemperature(AV102,ifavailable)
• OccupancyCommand(MV10)
• SystemMode(MV16)
• AuxiliaryOutputStatus(BO98)
• PIHeatingDemand(AO21)
• PICoolingDemand(AO22)
• WindowAlarm(BV35)
• FilterAlarm(BV36)
• ServiceAlarm(BV37)
Figure-1 GUI Example - VT8600UXBXX
Figure-2 GUI Example - VT8600UXBXX
Occupancy
System mode
Outdoor Temperature
Occupied
Heat
42
o
F
PI Heat
53%
Fan Status
On
Filter Alarm
Normal
PI Cool
0%
Room Temperature
Occupied Heating Setpoint
Occupied Cooling Setpoint
Unoccupied Heating Setpoint
Unoccupied Cooling Setpoint
71.2
o
F
71.0
o
F
73.0
o
F
62.0
o
F
82.0
o
F
Supply Temperature 42
o
F
Occupancy
System mode
Outdoor Temperature
Occupied
Cool
80
o
F
PI Heating Demand
53%
Supply Temperature 65.2
o
F
PI Cooling 78%
Demand
Room Temperature
Occupied Heating Setpoint
Occupied Cooling Setpoint
Unoccupied Heating Setpoint
Unoccupied Cooling Setpoint
74.2
o
F
71.0
o
F
73.0
o
F
62.0
o
F
82.0
o
F
Supply Temperature (AI11)
65.2
o
F
Vista de pagina 21