VT8000 Controller Replacement Guide
© 2014 Viconcis Technologies. All rights reserved.
Object Name Default Configurations
Current Configurations
before Replacement
Temporary Occupancy Time 2H
Dehumidification Hysteresis 5%
Dehumidification Max Cooling 100%
Dehumidification Lockout Enabled
4/7 Configuration
CPH 4
Control Type Floating
BO8 Out Time 15 Minute
BO8 AuxOut Not Used
Floating Time 1.5 min
DA /RA DA
5/7 Configuration
Proportional Band 3°F (1.2°C)
Pipe Number 2
Sequence of Operation Heat only
Purge Sample Period 2 hours
Purge Open 2 Minutes
6/7 Configuration
Main Password 0
User Password 0
Calib. Temperature 0.0 °C
Calib. Humidity 0.0 %RH
1/2 Setpoints
Unoccupied Cool Setpoint 80°F (26.5°C)
Standby Cool Setpoint 78°F (26°C)
Occupied Cool Setpoint 75°F (24°C)
Occupied Heat Setpoint 72°F (22°C)
Standby Heat Setpoint 69°F (21°C)
Unoccupied Heat Setpoint 62°F (16.5°C)
2/2 Setpoints
Default Heating Setpoint 72°F (22°C)
Minimum Deadband 2°F (1°C)
Max. Heating limit 90°F (32°C)
Min. Cooling limit 54°F (12°C)
Dehumidify 50 %RH
1/2 Display
User HMI 0
Color White
Main Display Temperature
Use Standby Screen No
Long message background color White
2/2 Display
Display Language English