Fan Coil Unit Controller SeriesApplication Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514 ) 321-4150
028-0444-01 www.viconics.com | sales@viconics.com February 2015
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8
- Aux Heat
OU9 - Close Cool V
UO10 - Close Heat V
UO11 - Open Cool V
UO12 - Open Heat V
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Modulating & PWM Control
COMM ON
24 VAC
FCU Low-voltage
TERMINAL BLOCK
DUCT HEATER, SRC
0-10 V 24V Com.
PERMETER HEAT
SOLID STATE RELAY
ZONE DAMPER
COOLING ONLY
ACTUATOR
0-10 V 24V Com.
S
L
Sequence of Operation and Wiring
Occupied Mode
During Occupied periods, occupied heating and cooling setpoints
are used.
Stand-by Mode (only available when PIR motion detector
sensor is used)
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which
automatically switches occupancy levels from occupied to stand-by
to unoccupied when no motion is detected in the room:
• During PIR activated stand-by periods, stand-by heating and
cooling setpoints are used.
• During PIR activated unoccupied periods, the unoccupied-by
heating and cooling setpoints are used.
Unoccupied Mode
During unoccupied periods, unoccupied heating and cooling
setpoints are used.
Local Override
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.
On Call for Heat
The damper remains closed. The proportional heater acts as a first
step and modulate from 0 to 100% capacity. The perimeter heater
operates as a second step.
On Call for Cool
The damper modulates from closed to open according to demand.
Options
• Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
• Remote wall mounted sensor or return air temperature
sensor can be used instead of internal temperature sensor of
Controller.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.