Date
Occupancy Status
Indoor Temperature
Indoor Humidity
Outdoor Temperature
System Mode
Short Network
Message
VT8300 Series
Installation Guide
10
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: ( 514) 321-4150
028-0429-02 www.viconics.com | sales@viconics.com February 2015
©2015 Viconics Technologies Inc. All rights reserved.
Wiring examples of 2 remote room sensors for averaging applications:
Wiring examples of 3 remote room sensors for averaging applications:
Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10K±3%, B25/85°C = 3975K±1.5%)
ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm
-40 -40 324.3197 -20 -4 94.5149 0 32 32.1910 20 68 12.4601 40 104 5.3467
-35 -31 234.4009 -15 5 71.2430 5 41 25.1119 25 77 10.0000 45 113 4.3881
-30 -22 171.3474 -10 14 54.1988 10 50 19.7390 30 86 8.0694 50 122 3.6202
-25 -13 126.6109 -5 23 41.5956 15 59 15.6286 35 95 6.5499 55 131 3.0016
Common
UI 20
BO8
24 Vac Com
UI17
VT8300
Series Controller
1 x S3010W1000 & 1 x S3020W1000
Remote wiring 2 sensor
S2-1= On, S2-2=Off
SCom
RS
Aux
C
DI
SCom
RS
Common
UI 20
BO8
24 Vac Com
UI17
VT8300
Series Controller
2 x S3020W1000
Remote wiring 2 sensor
S2-1= On, S2-2=Off
SCom
RS
Aux
C
DI
SCom
RS
Common
UI 20
VT8300
Series Controller
2 x S3010W1000
Remote wiring 2 sensor
S2-1= On, S2-2=Off
SCom
RS
SCom
RS
Notes for averaging applications:
• S3010W1000andS3020W1000canbe
mixedmatched.
• S3010W1000andS3020W1000aretobe
wiredinparallel.
• Respectthedipswitchsettingineach
remotesensor.
Dip switch
setting for:
2 sensors
S2-1 = ON
S2-2 = OFF
Common
UI 20
BO8
24 Vac Com
UI17
VT8300
Series Controller
2 x S3010W1000 & 1x S3020W1000
Remote wiring 3 sensor
S2-1= Off, S2-2=Off
SCom
RS
Aux
C
DI
SCom
RS
SCom
RS
Common
UI 20
VT8300
Series Controller
3 x S3010W1000
Remote wiring 3 sensor
S2-1= Off, S2-2=Off
SCom
RS
SCom
RS
SCom
RS
Dip switch
setting for:
3 sensors
S2-1 = OFF
S2-2 = OFF
ON
1 2
ON
1 2
Vista de pagina 9
1 2 ... 5 6 7 8 9 10 11 12 13

Comentarios a estos manuales