Objects Table
Device object properties supported
Object Property VWG Parameter
Object_Identifier
Property 75 (R)
Unique ID number of a device on a network
Object_Name
Property 77 (R,W)
Unique name of a Device on a network
Model Name
Property 70 (R)
VWG Model number
Location
Property 58 (R,W)
Default value is: Unknown
Description
Property 28 (R,W)
Default value is: Viconics Wireless Gateway
Firmware Revision
Property 44 (R)
Current BACnet firmware revision used by the VWG
Protocol Version
Property 98 (R)
Current BACnet firmware protocol version
Default is Version 1
Protocol Revision
Property 139 (R)
Current BACnet firmware protocol revision
Default is Revision 4
Max ADPU Length
Property 62 (R)
Maximum ADPU Length accepted
Default is 480
ADPU Timeout
Property 10 (R)
ADPU timeout value
Default is 3000 ms
Max_Master
Property 64 (R)
Maximum MAC address the device will poll for master on the MS-TP
network. 0 to 127, default is 127
Max_Info_Frame
Property 63 (R)
Maximum number of frames allowed in one token by the VWG, default is
20
Local Time
Property 57 (R,W)
VWG local time
Local Date (R,W)
Property 58 (R,W)
VWG local date