SED-WIN/SED-DOR
Wireless Door/Window Switch
4
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0415-01 www.viconics.com | [email protected] November 2014
Pairing Process Procedure
NOTE: See VTR/VT installation manual for details on PAN ID parameter.
PAN ID for Centralized Networked Applications with MPM:
VT8000 Series VT7000 Series
1 - 500 1 - 250
PAN ID for Stand-alone Applications with no MPM:
VT8000 Series VT7000 Series
501 - 1000 N/A
Special note for all VT7000 Room Controllers: The VT7000 Room Controllers are only
compatible within a SmartStruxure network with MPM Controllers
Configuring Actions
Short Switch Duration Result
Approx. 1 second Enter Pairing Mode (page 8)
Approx. 1 second (after being paired) Displays MAC address (page 8)
4+ seconds and less than 10 seconds Battery Status (page 13 )
10+ seconds and less than 20 seconds Diagnostic Mode (page 12)
20+ seconds Resets Switch
Using VT8000 Controllers for Stand-alone Systems
When PAN ID is used with Range of 501 - 1000 for Stand-Alone Systems
In this application, the VT8000 controller(s) are the coordinators to their own systems and are
network masters for each wireless switch reporting to them. A unique network is needed for proper
functionality according to the following:
Wireless controller factory default Channel and PAN ID = controller(s) offline.
Each VT8000 controller is its own network coordinator.
Range of PAN ID on all controllers to use is 501 - 1000. This range is reserved for stand-alone
system operation.
Notes:
Each VT8000 Controller uses a unique PAN ID and/or Channel settings.
If all available PAN ID’s are used (501-1000), use a different channel.
Up to 20 switches can be linked to each VT8000 Controller.
The MAC address is only used to confirm parent pairing.
Coordinator
VT8000 Series Controller
Channel: 15 PAN ID: 501
Coordinator
VT8000 Series Controller
Channel: 15 PAN ID: 502
Coordinator
VT8000 Series Controller
Channel: 15 PAN ID: 503
Window or Door Switch Window or Door Switch Window or Door Switch
Figure-6 Stand-alone VT8000 series systems