Viconics BACnet Zoning System Engineering Guide Specification
Sequence of Operation – The Viconics BACnet Zoning System shall operate in the following manner: 1. The VZ7656x1000B Rooftop Unit controller sha
Sequence for economizer on VZ7656E1000B only: The fresh air damper can be controlled through more than one sequence to achieve different control st
Economizer Mode and CO2 Level Control If the fresh air damper is to be used for both free cooling and CO2level control (economizer mode and CO2 lev
Viconics BACnet Zoning System Engineering Guide Spec 1.01 System Description – The Viconics BACnet Zoning System (VBZS) shall provide a simple
(4000 feet), repeaters shall be used to ensure proper communication. With repeaters and a BACnet MS_TP supervisory system, the maximum number of no
VZ7656x1000B BACnet Rooftop or Heat Pump Controller The Rooftop unit Controller shall be: VZ7656R1000B: Up to two heating and two cool stages, si
The controller shall be capable of operating the packaged unit even if there is a loss of communication with the zone controllers. The packaged u
The controller shall have the ability to set the programmed occupied schedule time as the time at which the desired occupied temperature setpoin
Packaged unit controller model dependent specifications: VZ7656R1000B: Up to two heating and two cool stages, single fan speed output, 0-10Vdc out
BACnet Zone Controller VZ7260 Zone Controller – The zone controller shall be capable of controlling a local VAV analog damper actuator as well
The zone controller shall have a binary input that can be configured as follows: BI1 Binary input no.1 configuration Default: None (None): No func