Parameter Variable Name Function
fan mode 0 = On
1 = Auto
2 = Smart
0 = On
fan control 0 = Off
1 = On
1 = On
fan delay 0 = Off
1 = On
0 = Off
keypad lockout 0 = No_Lockout
1 = Level_1
2 = Level_2
No_Lockout
proportional band 2 to 8 F 2 F
temperature units 0 = °C
1 = °F
°F
frost protection 0 = Off
1 = On
0 = Off
temperature scale 0 = °C
1 = °F
°F
This configuration property defines the thermostat’s common
configuration parameters and their settings.
Valid Range and Default values:
Name Valid Range Default value
di1 configuration 0 = None
1 = RemNSB
2 = RemOVR
3 = Filter
4 = Service
0 = None
auxiliary contact
configuration
0 = NORMALLY_OPEN
1 = NORMALLY_CLOSE
0 =
NORMALLY_OPEN
number of events 2 or 4 2
progressive
recovery enable
0 = Off
1 = Active
0 = Off
number of heating
stages
1 = 1 Stage
2 = 2 Stages
2
number of cooling
stages
1 = 1 Stage
2 = 2 Stages
2
rh frontal display 0 = Off
1 = On
Off
humid low reset
temp
–40°F up to 15°F (-40°C
to –9.5°C)
-20.2°F (-29°C)
humid high reset
temp
20°F to 55°F (-6.5°C to
13°C)
32°F (0°C)
dehum lockout
temp
–40°F to 122°F (-40°C to
50°C)
32°F (0°C)
humidification high
limit setpoint
50% RH to 90% RH 85% RH
humid low reset rh
setpoint
10% RH to 90% RH 20% RH
dehumidification
hysterisys
2% RH to 20% RH 5% RH
rh sensor
calibration
–15% RH to 15% RH 0% RH
humidification
setpoint
10% RH to 90% RH 50% RH
dehumidification
setpoint
15% RH to 95% RH 70% RH
Thermostat’s
common
configuration
parameters
network input
config
UNVT_cfg_3_rtu_hp
nciCfg3RtuHp
dehumidification
lockout function
0 = Off
1 = On
1 = On