Parameter Variable Name Function
Occupied
Cool & Heat
Setpoints
network Input
SNVT_temp_p
nviSetpoint
This input network variable is used to allow the occupied
temperature setpoints only to be changed via the network from a
single analog value. (Note: the Unoccupied setpoints are not
changed). The corresponding heating and cooling values are
derived from the minimum deadband configuration value
Default Null Value: 621.81°F (327.67°C or 0x7FFF)
Ex. If the minimum deadband configuration value = 2 °F and
nviSetpoint = 70°F.
The resulting Occupied heating setpoint will equal 69 °F which is
derived from 70 °F minus ½ the minimum deadband configuration
value of 2 °F
The resulting Occupied cooling setpoint will equal 71 °F which is
derived from 70 °F plus ½ the minimum deadband configuration
value of 2 °F
This input network variable is used to set the time and date of the
Space Comfort Controller.
Default Null Value :
Sub Name Valid Range Default Value
1 year 0 to 3000 0
2 month 0 to 12 0
3 day 0 to 31 0
4 hour 0 to 23 0
5 minute 0 to 59 0
Date and
time
network input
SNVT_time_stamp
nviTimeSet
6 second 0 to 59 0