VT73xxX Integration Graphical User Interface (GUI) Objects
The following objects should be typically used in a GUI:
Room Temperature (AV7);
Occupied and Unoccupied Heat Setpoints (AV 39 and AV43);
Occupied and Unoccupied Cool Setpoints (AV 40 and AV34);
Room Humidity (AV10) (If available);
Room Humidity Setpoint (AV 71) (If available);
Outdoor Temperature (AV 9);
Supply Temperature (AI12) (If available);
Occupancy Command (MV18);
System Mode (MV16);
Fan Mode (MV17);
Fan Status (MV28);
Output 2 (MV26);
Output 1 (MV28);
PI Heating Demand (AV21)
PI Cooling Demand (AV22)
Window Alarm (BI 35);
Filter Alarm (BI 36);
Service Alarm (BI 37);
Figure 2: Example of a graphical user interface