4A) (SA) Stand-Alone applications
When PAN ID is used with a range of 251 to 500, for (SA) Stand-Alone Systems.
In this application, the VZ76xx controller(s) act as the coordinators to their own system. I.E. they are the
network masters for each VZ72xx controller reporting to them when the whole zoning system(s) is self
sufficient and communication and no external communication is required.
Wireless controller factory default Channel and PAN ID = Controller(s) offline
VZ76xx RTU controller is the network coordinator
Range of PAN ID on all controllers to use 251 to 500. This range is reserved for stand-alone system
operation
System 1
Examples:
RTU VZ76 Coordinator
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
Zone VZ72 Router
Channel
25
ID
200
System 2
RTU VZ76 Coordinator
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
Zone VZ72 Router
Channel
25
ID
205
Notes:
· Each system with a VZ76xx RTU master will use a unique PAN ID and or channel settings