Viconics VWZS Integration Guide Manual de usuario Pagina 69

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 70
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 68
69
VT76xxX Integration Graphical User Interface (GUI) Objects
The following objects should be typically used in a GUI:
Room Temperature (Numeric);
Occupied and Unoccupied Heat Setpoints (Numeric);
Occupied and Unoccupied Cool Setpoints (Numeric);
Outdoor Temperature (Numeric);
Supply Temperature (Numeric) (If available);
Occupancy Command (Enum);
Effective Occupancy (Enum);
System Mode RTU (Enum) or System Mode HPU (Enum);
G Fan (Boolean);
Y1 Cool (Boolean);
Y2 Cool (Boolean);
W1 Heat (Boolean);
W2 Heat (Boolean) or Reversing Valve (Boolean);
Economizer Output (Numeric) (if available);
Aux (Boolean);
DI 1 Status (Boolean);
DI 2 Status (Boolean);
Frost Alarm (Boolean) (if available);
Filter Alarm (Boolean) (if available);
Service Alarm (Boolean) (if available);
Fan Lock Alarm (Boolean) (if available);
(BI 38)
(AV22)
(BI 25)
(BI 26)
(BI 27)
(BI 28)
(BI 29)
(MV 12)
(MV 14)
(BI 24)
(BI 31)
(BI 32)
(BI 36)
(BI 39)
(AI 16)
(AV 42)
(AV 43)
(AV 44)
(AV 45)
(AV 45)
(AV 45)
Typical GUI for a VT7605B5000W with Economizer control