6 | VZ7260B Series - Installation Guide
TERMINAL, IDENTIFICATION AND FUNCTION
Wiring
Terminal Use
Terminal
Identification
VZ7260F
Terminal
Identification
VZ7260C
Description
4 - 24 V ~ Hot
24V ~Hot 24V ~Hot
Power supply of controller, hot
side (Delivered from the RTU).
5 - 0 V ~ Com
0V~Com 0V~Com
Power supply of controller,
common side. Also used as
reference for the analog
outputs when used.
6- On-Off Rht
BO5 BO5
Local isolated triac reheat
output when used.
7- On-Off Rht
BO5 BO5
Local isolated triac reheat
output when used.
8- Primary Rht
Not used
BO3
24 VAC triac reheat output
(open).
9 – Primary
Rht
AO2 BO4
For VZ7260F: Local analog 0 -
10 VDC reheat output when
used.
For VZ7260C: 24VAC triac
reheat output (close).
10 VAV
Damper
AO1 BO1
For VZ7260F: Local VAV
analog 0 - 10 VDC.
For VZ7260C: 24VAC triac
VAV output (open).
11 VAV
Damper
Not used BO2
24VAC triac reheat output
(close).
12 BI1
BI1 BI1
Configurable extra digital
input. See parameter section
for more information.
13 AI4
AI4
AI4
0-10VDC analog input for
remote CO2 or other sensor
(airflow, etc...)
14 - Scom
Scom Scom
Reference input for BI 1, BI 2,
UI3 and RS.
15 - RS
RS RS
Remote room sensor input
when used. Input auto-detects
a remote sensor and will
automatically by-pass the
internal sensor when used.
16 UI3 / SS
UI3 UI3
Non-configurable extra analog
input for monitoring local
discharge or supply
temperatures over the
network.
BACnet™ Network Connections
BACnet™ Com
Com +
BACnet™ communication bus + connection.
BACnet™ Com
Com -
BACnet™ communication bus connection.
Ref
Ref
Communication bus reference terminal.
o DO NOT USE FOR OTHER THAN
SERVICING ISSUES
o DO NOT WIRE SHIELD TO THIS
TERMINAL