16 | VZ7260W Series- Installation Guide
Configuration Parameters
Default Value
Significance and Adjustments
PswrdSet
Configuration parameters
menu access password
Default value = 0
No password prompted
This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000
Zone MAC
Zone Controller Controller
network address
Default Value: 255
RTC MAC address must be unique for the entire
network.
1 to 255 (Increments: 1 or 10)
For BACnet models valid range to use is from 1 to
127.
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 500
This parameter (Personal Area Network Identification) is
used to link specific controllers to a single specific
Viconics wireless gateway ( VWG / Jace-Driver ) or a
specific VZ76 RTU controller. For every controller
reporting to a VWG / Jace-Driver or VZ76 controller, be
sure you set the SAME PAN ID value.
The default value of 0 is NOT a valid PAN ID. The valid
range of available PAN ID is from 1 to 500