Configuration Properties (nci’s) Description
Parameter Variable Name Function
This configuration property defines the space temperature
setpoints for various heat, cool and occupancy modes.
Valid Range and Default values:
Sub Name Valid Range Default value
01 occupied_cool 54 to 100°F
(12 to 37.5°C)
75°F (24.0°C)
02 standby_cool 54 to 100°F
(12 to 37.5°C)
78°F (25.5°C)
03 unoccupied_cool 54 to 100°F
(12 to 37.5°C)
80°F (26.5°C)
04 occupied_heat 40 to 90°F
(4.5 to 32°C)
72°F (22.0°C)
05 standby_heat 40 to 90°F
(4.5 to 32°C)
69°F (20.5°C)
Temperature
Setpoints
network input config
SNVT_temp_setpt
nciSetPts
06 unoccupied_heat 40 to 90°F
(4.5 to 32°C)
62°F (16.5°C)
This configuration property defines the space humidity parameters
and their settings.
Valid Range and Default values:
Sub Name Valid Range Default value
01 bi1 config 0 = None
1 = Rem NSB
2 = Motion NO
3 = Motion NC
4 = Window
0 = None
02 bi2 config 0 = None
1 = Door Dry
2 = Override
3 = Filter
4 = Service
0 = None
03 ui3 config 0 = None
1 = COC/NH
2 = COC/NC
3 = COS
4 = SS
0 = None
04 room humidity display 0 = Not active
1 = Active
0 = Not active
05 dehumidification
setpoint
30 to 100% RH 50% RH
06 dehumidification
hysterisys
2 to 20% RH 5% RH
07 dehumidification max
cooling
20 to 100% RH 100% RH
RH Model
Options
network input config
UNVT_cfg_2_fcu_zn
NciCfg2FcuZn
08 calib room humidity
sensor
-15 to +15% RH 0% RH