Manual Identification
Neuron ID of a device can also be entered manually through a commissioning or service tool. Neuron ID should
be located on the Echelon chip of the device being commissioned.
Figure 8 shows an example of a Manual Neuron ID request made through a commissioning tool.
Figure 8: Manual Neuron ID request
Tips And Things You Need To Know
In order to operate nviAuxOut (auxiliary output) from the network, Aux contact configuration (Auxcont
nciGenOpt) needs to be set as “Network Controlled”;
If the heartbeat is lost, the module will release the network sensor value for the Room Temperature
(nviSpaceTemp) and the Outdoor Temperature (nviOutdoorTemp);
The SeqOpera value (Sequence of Operation) depends on the nviHeatCool value and nviAuxHeatEnable
value. See note 1 on page 15 for all the details;
Troubleshooting Section
Error / Trouble
Condition
Possible Cause Solution
The LON network has too many
devices.
Do not exceed the maximum number of
devices and maximum length allowed
by the EIA-485 specifications.
Too many devices were installed
without any repeaters.
Repeaters need to be installed as
specified in this document.
The LON cable runs are broken Locate the break and correct wiring
Thermostat does not
come online
The thermostat does not have power Apply power to the thermostat
Document Control
Document Name: ITG-VT72_73-PIR-LON E07
Document Filename: ITG-VT72_73-PIR-LON E07.pdf
Revision Date Changes
01 January 4, 2006 Created to coincide with release of the VT7300 as a LonMark certified product.
02 April 5, 2006 Updated the DRF files section and removed any application guide reference
03 July 11, 2006 Modified the Software Files section and added the RoHS / Non-RoHS section
04 Aug 15, 2006 Modified Note 1 on page 15
05 Nov 21, 2007 Added modifications required for PIR support to the new VT73xxX5xxxE release
06 Jan 21, 2008 Added additional modifications required for PIR support
07 Feb 03, 2009 Added changes for new PID supported 80:00:C5:55:00:04:04:20
Added revision history table for all VT7200X & VT73xxX PID’s
Vista de pagina 26
1 2 ... 22 23 24 25 26 27

Comentarios a estos manuales

Sin comentarios