Viconics VT8600 Series BACnet Integration Guide Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 41
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
VT8600 Series BACnet
®
Integration Manual
17
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: (514 ) 321-4150
028-0437-00 www.viconics.com | sales@viconics.com March 2015
© 2015 Viconics Technologies Inc. All rights reserved.
PROPERTY VALUE RANGE RESTRICTIONS FOR MSI OBJECTS
Object Name Object Type Instance Index Text Default Value
BACnet Status MSI 1
1 Offline
Offline
2 Online
ZigBee Status MSI 2
1 Not Detected
N/A
2 Power On
3 No Network
4 Joined
5 Online
Effective Occupancy MSI 33
1 Occupied
Occupied
2 Unoccupied
3 Override
4 Standby
Wireless Zone 1 Status MSI 210
1 None
None
2 Closed
3 Opened
4 Motion
5 No Motion
Wireless Zone 1 Battery MSI 211
1 None
None2 Normal
3 Low
Wireless Zone 1 Paired MSI 212
1 No
No2 Yes
3 Invalid
Wireless Zone 2 Status MSI 220
1 None
None
2 Closed
3 Opened
4 Motion
5 No Motion
Object Name Object Type Instance Index Text Default Value
Wireless Zone 10 Set Function MV 300
1 None
None
2 Window
3 Door
4 Motion
5 Status
6 Remove
PROPERTY VALUE RANGE RESTRICTIONS FOR MV OBJECTS