INTEGRATION – GLOBAL COMMANDS
The following figure shows which objects from the controller can be monitored and controlled from the BAS front-end.
Outdoor Temperature (AV101)
System mode (MV16)
Occupancy Command (MV10)
Fan Mode (MV17)
Occupied Heating Setpoint (AV39)
Unoccupied Heating Setpoint (AV43)
Occupied Cooling Setpoint (AV40)
Unoccupied Cooling Setpoint (AV44)
Main Password (AV56)
Room Temperature (AV100)
MS/TP
Network
BAS
Front End
VT8600 Series
controller
Global Command Control Level Device Level
Figure 1 : Global commands from a BAS front-end to a typical VT86xx series controller
Note: For information about integrating ZigBee wireless sensors with BACnet, refer to the
ZigBee Wireless Sensor Installation Guide.
All Devices
(All controllers)
Outdoor Temperature
Outdoor Temperature and HVAC plant current mode
Specific Devices
(Specific area controllers)
Schedule
Schedule
Outdoor Temperature
Restrict user access to controller
Room temperature for testing and override