
VT8600 SeriesUser Interface Guide
20
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-00 www.viconics.com November 2014
© 2014 Viconics Technologies. All rights reserved.
CONFIGURATION PARAMETERS SCREEN 4/9
PARAMETER DETAILS SCREEN 4/9
Configuration Parameters Default Value Significance and Adjustments
Cooling CPH
Cooling stages cycles per hour.
Default value: 4 CPH
Sets the maximum number of cooling stage cycles per hour under
normal control operation. It represents the maximum number of
cycles that the equipment will turned on and off in one hour.
Note that a higher CPH will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
3 or 4 CPH
For multi stage models, cool CPH applies to Y1 & Y2
Heat CPH
Heating stages cycles per hour.
Default value: 4 CPH
Will set the maximum number of heating stage cycles per hour
under normal control operation. It represents the maximum number
of cycles that the equipment will turn ON and OFF in one hour.
Note that a higher CPH will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
3, 4, 5, 6,7 & 8 CPH
For multi stage models, heat cph applies to W1 & W2
Comentarios a estos manuales