TEST OUTPUTS
Note: screen Test outputs are LIVE. Any output gets displayed immediately for any value change according to the following:
1. If any BACnet priority array (1 - 16) includes a value, the displayed state background shows in red.
2. When toggling a value on the screen, the output directly energizes according to the selected value.
3. You can override any output if you bypass the Bacnet array (1 - 16).
4. It is not possible to modify the set Bacnet array values.
5. After any output state gets modified, all overrides get cancelled after 1 minute of button inactivity, or if you scroll from one screen to
another screen.
CASE A: screen 2/2 display is dependent on Control type configuration. If mode is set to On/Off, binary options show.
CASE B: screen 2/2 display is dependent on Control type configuration. If mode is set to Analog, analog options show.