Configuration Parameters Default Value Significance and Adjustments
Main password
Default value: 0
Main Password
Installer password. This parameter sets a protective access
password to prevent unauthorized access to configuration menu
parameters.
Default value of 0 does not prompt a password or lock access
configuration menu.
Range: 0 - 9999.
User Password
Default value: 0
User Password
User password. This parameter sets a protective access password
to prevent user unauthorized access to main screen adjustments.
Default value of 0 does not prompt a password.
Range: 0 - 9999.
Schedule menu
Default value: Enabled
Toggles activation of schedule menu direct access
Enabled The Schedule Menu is directly accessible from the main
screen via a touch in the upper corner (see page 4).
Disabled The Schedule Menu can only be accessed through the
Setup Menu screens
Calib. temp.
Default value: 0.0 °C or °F
Calibration Temperature
Room temperature sensor calibration. Offset can be added or
subtracted to actual displayed room temperature.
Range: ± 2.5 °C, 0.5 °C increments (± 5.0 °F, 1.0 °F
increments).
Calib. OS temp.
Default value: 0.0 °C or °F
Calibration Outside Temperature
Outside air temperature sensor calibration. Offset that can be
added/subtracted to the actual displayed outdoor temperature.
Range: ± 2.5 °C, 0.5 °C increments (± 5.0 °F, 1.0 °F
increments).